    NOM-029-STPS Requirements for Medium Voltage Maintenance: Industrial Safety Technical Guide

    Eng. SINE MéxicoAugust 25, 20267 min read

    Requisitos de la NOM-029-STPS para mantenimiento de media tensión: Guía Técnica de Seguridad Industrial

    In the manufacturing sector of northern Mexico, particularly in regions with high energy demand such as Torreón, Saltillo, and Piedras Negras, operational continuity directly depends on the stability of our substations. However, intervening in a pad-mounted transformer, a capacitor bank, or a medium voltage distribution panel (from 1 kV to 35 kV) is not just any maintenance job. An error in protection coordination or an omission in the lockout protocol can cause an electrical arc (arc-flash) with fatal consequences and multimillion-dollar losses for the plant.

    To regulate these activities and ensure the physical integrity of technicians, the Ministry of Labor and Social Welfare implemented the NOM-029-STPS-2011. This standard is not a simple bureaucratic procedure; it is a strict operational framework that defines how we must plan, execute, and supervise each intervention in the electrical infrastructure.

    In this technical article, we will thoroughly analyze the requirements of the NOM-029-STPS medium voltage, from the preparation of the work plan to the selection of dielectric personal protective equipment and obtaining the necessary labor competency certificates to avoid severe fines during federal inspections.


    Table of Contents

    1. Introduction to NOM-029-STPS-2011 and its importance in medium voltage
    2. Who does NOM-029-STPS apply to in the Mexican industrial sector?
    3. Key requirements for the maintenance of medium voltage electrical installations
    4. Employer's obligations in medium and high voltage work
    5. Workers' obligations: Training and DC-3 certificate
    6. How to prepare an electrical safety Work Plan according to the standard
    7. Mandatory dielectric Personal Protective Equipment (PPE)
    8. Safety procedures for energized and de-energized lines
    9. Lockout/Tagout (LOTO) protocol in medium voltage
    10. STPS sanctions and fines for non-compliance with NOM-029
    11. Advantages and disadvantages of outsourcing electrical maintenance
    12. Common errors in the Mexican industry when applying NOM-029
    13. Real case: Major maintenance to a 13.8 kV substation in Saltillo
    14. Professional compliance checklist for STPS audits
    15. Frequently Asked Questions
    16. Conclusion and recommendations for STPS audits

    Introduction to NOM-029-STPS-2011 and its importance in medium voltage

    Industrial welding NOM-029-STPS-2011 establishes the minimum safety conditions for carrying out maintenance activities in electrical installations at workplaces. When we talk about medium voltage—which in Mexican industry typically covers operating voltages of 13.8 kV, 23 kV, and up to 34.5 kV—the risk level of an electric shock or a short-circuit detonation increases exponentially compared to low voltage.

    Industrial maintenance of electrical installations NOM-029-STPS-2011 is not optional. Its compliance seeks to mitigate the risk of arc flash, which can reach temperatures exceeding 19,000 °C (hotter than the surface of the sun), instantly vaporizing metals and projecting copper shrapnel and panel components at extreme speeds.

    In the context of heavy manufacturing in Coahuila and northern Mexico, where foundries, automotive plants, and large-scale maquiladoras operate, the correct implementation of this official Mexican standard for electrical installations is the only real line of defense between a routine maneuver and an industrial catastrophe.


    Who does NOM-029-STPS apply to in the Mexican industrial sector?

    This standard governs throughout the national territory and applies to all workplaces that carry out maintenance activities on electrical installations, whether permanent or temporary, and that operate under any voltage level.

    However, for practical purposes of fiscalization and technical scope, the requirements are divided according to the voltage level and the complexity of the network. If your plant has:

    • A medium voltage service entrance from the Federal Electricity Commission (CFE).
    • Electrical distribution substations (garden, pad-mounted, or compact type).
    • Power transformers.
    • Large capacity synchronous or induction motors operating at medium voltage.

    Then, you are obligated to comply with all the safety provisions for medium voltage electrical maintenance. This includes both internal maintenance personnel and external contractors you hire to perform lockouts or dielectric tests. It is worth noting that this compliance goes hand in hand with obtaining an approving opinion in the industrial electrical installations verification under NOM-001-SEDE-2012.

    To learn more about the general regulatory framework applicable to the manufacturing industry, you can consult our specialized section on regulations.


    Key requirements for the maintenance of medium voltage electrical installations

    The core of the standard requires that no maintenance activity be carried out improvisationally. To safely intervene in medium voltage infrastructure, the STPS requires three mandatory documentary and operational pillars:

    1. Potential Risk Analysis: A preliminary study identifying specific facility hazards, safety distances (approach boundaries), available incident energy (in $cal/cm^2$), and necessary control measures.
    2. Authorized Safety Procedures: Technical documents describing step-by-step how to perform each maneuver, from opening disconnect switches to temporary grounding.
    3. Specific Work Plan: A dynamic and signed document for each maintenance shift that defines work areas, authorized personnel, and lockout/tagout release signatures.

    Engineer's Tip: Do not confuse the general plant risk analysis with the specific electrical risk analysis for medium voltage. The latter must be based on recognized methodologies (such as NFPA 70E or IEEE 1584) to accurately determine the arc flash hazard category in each cabinet.


    Employer's obligations in medium and high voltage work

    In accordance with the NOM 029 STPS requirements, the employer (or plant management) is legally and operationally responsible for ensuring a safe environment. Their main obligations include:

    • Have the Work Plan: Keep it updated and available for maintenance crews.
    • Provide adequate PPE: Supply, at no cost to the worker, the dielectric and arc flash personal protective equipment specific to the incident energy level determined in the study. arc-flash.
    • Authorize workers in writing: Issue written authorizations only to personnel who demonstrate having the required technical and medical training.
    • Have updated single-line diagrams: Keep the plant's single-line diagram up to date, with CFE nomenclature and specifications for protection devices, load schedule, and grounding.
    • Supervise contractors: Ensure that external maintenance companies strictly comply with NOM-029-STPS and present their current training records.

    Workers' obligations: Training and DC-3 certificate

    Electrical safety is not unilateral. Electricians and assistants who work on medium voltage lines must fulfill critical responsibilities:

    • Participate in training: Attend electrical safety and first aid courses focused on rescue in energized zones.
    • Have the DC-3 NOM 029 certificate: Every worker performing medium voltage maneuvers must possess a Certificate of Competencies or Labor Skills (DC-3 Format) issued by an external training agent registered with the STPS, which validates their specific knowledge of NOM-029-STPS-2011.
    • Use and care for PPE: Visually inspect their equipment (especially dielectric gloves before each use using the inflation test) and report any anomaly.
    • Follow the instructions of the Work Plan: Do not perform any maneuver that is not explicitly authorized in the work document or that alters the established safety sequence.

    How to prepare an electrical safety Work Plan according to the standard

    Industrial The NOM 029 STPS work plan is the roadmap that prevents human error of omission during the pressure of a plant shutdown for maintenance.

    Mandatory Work Plan Structure:

    1. General Data: Name of the workplace, execution date, detailed description of the activity (e.g., Preventive maintenance for a 1000 kVA transformer).
    2. Personnel Involved: Name, position, and signature of the person responsible for the work, the executors, and the person authorizing the lockout/tagout.
    3. Specific Risk Analysis: Identification of hot spots, safety distances, and voltage level of the parts to be worked on.
    4. Maneuver Sequence: Chronological description of disconnection, lockout, verification of absence of voltage, and grounding.
    5. Protective Equipment and Tools: List of hot sticks, voltage detectors, temporary physical grounding sets, and insulated tools to be used.
    6. Emergency and Rescue Plan: Location of the first aid kit, rigid stretcher, dielectric rescue hook, and emergency numbers (including CFE and local medical services).

    Mandatory dielectric Personal Protective Equipment (PPE)

    The use of common cotton clothing or standard industrial footwear is completely insufficient for medium voltage. The dielectric and arc flash personal protective equipment must be selected based on the incident energy calculation of the installation.

    PPE ComponentRequired Technical SpecificationMain Function
    Dielectric HelmetClass E (according to NOM-